240W Single Output Industrial DIN RAIL Power Supply DRP-240 series
Features:
* Universal AC input / Full range
* Built in active PFC function
* Protections: Short circuit / Overload / Over voltage / Over temperature
* Cooling by free air convection
* Can be installed on DIN rail TS-35/7.5 .or 15
* UL 508(industrial control equipment)approved
* LED indicator for power on
* 100% full load burn-in test
* Fixed switching frequency at 100KHz
* 3 years warranty
Specifications:
MODEL
|
DRP-240-24
|
DRP-240-48
|
OUTPUT
|
DC VOLTAGE
|
24V
|
48V
|
CURRENT RANGE
|
0 ~ 10A
|
0 ~ 5A
|
RATED CURRENT
|
10A
|
5A
|
RATED POWER
|
240W
|
240W
|
RIPPLE & NOISE
|
80mVp-p
|
150mVp-p
|
VOLTAGE ADJ. RANGE
|
24 ~ 28V
|
48 ~ 53V
|
VOLTAGE TOLERANCE
|
1.0%
|
LINE REGULATION
|
0.5%
|
LOAD REGULATION
|
1.0%
|
SETUP RISE
TIME
|
800ms, 40ms/230VAC 800ms, 40ms/115VAC at full load
|
HOLED UP TIME
|
24ms/230VAC 24ms/115VAC at full load
|
INPUT
|
VOLTAGE RANGE
|
85 ~ 264VAC 120 ~ 370VDC
|
FREQUENCY RANGE
|
47 ~ 63Hz
|
EFFICIENCY
|
84%
|
85%
|
AC CURRENT
|
2.8A/115VAC 1.4A/230VAC
|
INRUSH CURRENT
|
COLD START 27A/115VAC 45A/230VAC
|
LEAKAGE CURRENT
|
<3.5mA / 240VAC
|
PROTECTION
|
OVER LOAD
|
105 ~ 160% rated output power
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
SHORT CIRCUIT
|
|
OVER VOLTAGE
|
30 ~ 36V
|
54 ~ 60V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
OVER TEMP
|
100 5 (TSW1)detect on heat sink of power transistor
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
OTHERS
|
MTBF
|
289.9Khrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
125.5*125.2*100mm (W*H*D)
|
PACKING
|
1.2Kg; 12pcs/15.5Kg/1.29CUFT
|