Category
Tiger Jazz
LED Driver
Online Service
Contact Us
|
DR-RDN20
20A Power Supply Redundancy Module
Features: * Suitable for redundant operation of 24V system
* Installed on DIN Rail TS35 / 7.5 .or 15
* Relay contact signal output and LED indicator for input failure alarm
* Cooling by free air convection
* 3 years warranty Specifications: MODEL DR-RDN20 OUTPUT REVERSE VOLTAGE(MAX) 30V OUTPUT CURRENT(MAX) 20A VOLTAGE DROP 0.5V LED INDICATORS Two green LEDs indicating each input is "OK .or fail" INPUT INPUT VOLTAGE RANGE 21 ~ 28V NUMBER OF INPUTS TWO INPUT CURRENT(MAX) 20A per input FUNCTION INPUT VOLTAGE ALARM When input is > 20V( 5%) .or < 30V( 5%) relay contacts RELAY CONTACT RATING 30VDC, 1A ENVIRONMENT WORKING TEMP. -20 ~ +70 WORKING HUMIDITY 20 ~ 90% RH non condensing STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mouning: Compliance to IEC60068-2-6 ENVIRONMENT WITHSTAND VOLTAGE Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC ISOLATION RESISTANCE Terminal-Chassis :>100M Ohms/500VDC 25 70%RH EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8, ENV50204, Heavy industry level, criteria A OTHERS MTBF 996.8Khrs min. MIL-HDBK-217F (25 ) DIMENSION 55.5*125.2*100mm (W*H*D) PACKING 0.5Kg; 20pcs/11Kg/1.29CUFT