Hangzhou Showland Power Co.,Ltd

DR-100

DR-100,
DR-100
  • Product:
    DR-100

  • Model Number:


  • Description:
     


    Learn more about products detailed description, pricing and service, Please send mail to us!

    sales@showlandpower.com
100W Single Output Industrial DIN Rail Power Supply DR-100 series

Features:
*  Universal AC input / Full range
*  Protections: Short circuit / Overload / Over voltage / Over temperature
*  Cooling by free air convection
*  Can be installed on DIN rail TS-35/7.5 .or 15
*  Isolation class
*  LED indicator for power on
*  No load power consumption<1W
*  100% full load burn-in test
*  3 years warranty

Specifications:

MODEL

DR-100-12 

DR-100-15 

DR-100-24

 

 

 

OUTPUT

DC VOLTAGE

12V

15V

24V

CURRENT RANGE

0 ~ 7.5A

0 ~ 6.5A

0 ~ 4.2A

RATED CURRENT

7.5A

6.5A

4.2A

RATED POWER

90W

97.5W

  100.8W

RIPPLE & NOISE

120mVp-p

120mVp-p  

150mVp-p

VOLTAGE ADJ. RANGE

12 ~ 15V 

15 ~ 18V

24 ~ 29V

VOLTAGE TOLERANCE

2.0%

1.0%

1.0%

LINE REGULATION

1.0%

LOAD REGULATION

1.0%

SETUP, RISE TIME

2700ms, 80ms/230VAC    2700ms, 80ms/115VAC at full load

HOLD UP TIME 

50ms/230VAC     18ms/115VAC at full load

 

 

INPUT

VOLTAGE RANGE

88 ~ 264VAC   124 ~ 370VDC

FREQUENCY RANGE

47 ~ 63Hz

EFFICIENCY 

87%

87%

89%

AC CURRENT 

3A/115VAC     1.6A/230VAC

INRUSH CURRENT 

COLD START 30A/115VAC      45A/230VAC

 

 

PROTECTION

OVER LOAD

NOTE.6

105 ~ 135% rated output power

Protection type : Constant current limiting, recovers automatically after fault condition is removed

OVER VOLTAGE

16 ~ 20V

19 ~ 23V 

30 ~ 35V

Protection type : Shut down o/p voltage, re-power on to recover

OVER TEMPERATURE

90oC    15  (RTH2) detect on heatsink of power transistor

Protection type : Shut down o/p voltage, re-power on to recover

 

 

 ENVIRONMENT

WORKING TEMP.

-20 ~ +60oC (Refer to output load derating curve)

WORKING HUMIDITY

20 ~ 90% RH non-condensing

STORAGE TEMP., HUMIDITY

-40 ~ +85oC , 10 ~ 95% RH

TEMP. COEFFICIENT

0.03%/ oC(0 ~ 50oC )

VIBRATION

Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

 

 

 

 

SAFETY &EMC

SAFETY STANDARDS

UL60950-1, TUV EN60950-1 approved, design refer to EN50178

WITHSTAND VOLTAGE 

I/P-O/P:3KVAC

ISOLATION RESISTANCE

I/P-O/P:>100M Ohms / 500VDC / 25 / 70% RH

EMI CONDUCTION & RADIATION

Compliance to EN61204-3, EN55022 ClassB

HARMONIC CURRENT

Compliance to EN61000-3-2,-3

EMS

IMMUNITY

Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A

OTHERS

MTBF

486K hrs min. MIL-HDBK-217F (25oC  )

DIMENSION

100*93*56mm (W*H*D)

PACKING 

0.35Kg; 36pcs/13.6Kg/0.89CUFT