480W Single Output DIN RAIL with PFC Function DRP-480S series
Features:
* AC input range selectable by switch
* Built-in passive PFC function compliance to EN61000-3-2
* High efficiency 89% and low dissipation
* Protections: Short circuit / Overload / Over voltage / Over temperature
* Cooling by free air convection
* Built-in constant current limiting circuit
* Can be installed on DIN rail TS-35/7.5 .or 15
* UL 508(industrial control equipment)approved
* EN61000-6-2(EN50082-2) industrial immunity level
* 100% full load burn-in test
* 3 years warranty
Specifications:
MODEL
|
DRP-480S-24
|
DRP-480S-48
|
OUTPUT
|
DC VOLTAGE
|
24V
|
48V
|
CURRENT RANGE
|
0 ~ 20A
|
0 ~ 10A
|
RATED CURRENT
|
20A
|
10A
|
RATED POWER
|
4800W
|
480W
|
RIPPLE & NOISE
|
120mVp-p
|
120mVp-p
|
VOLTAGE ADJ. RANGE
|
24 ~ 28V
|
48 ~ 55V
|
VOLTAGE TOLERANCE
|
1.0%
|
LINE REGULATION
|
0.5%
|
LOAD REGULATION
|
1.0%
|
SETUP, RISE
TIME
|
1200ms, 40ms/230VAC at full load
|
HOLED UP TIME
|
23ms/230VAC,115VAC at full load
|
INPUT
|
VOLTAGE RANGE
|
90 ~ 132VAC/180 ~ 264VAC by switch 254 ~ 370VDC
|
FREQUENCY RANGE
|
47 ~ 63Hz
|
POWER FACTOR
|
0.7/230VAC only
|
EFFICIENCY
|
89%
|
89%
|
AC CURRENT
|
8A/115VAC 3.2A/230VAC
|
INRUSH CURRENT
|
COLD START 27A/115VAC 45A/230VAC
|
LEAKAGE CURRENT
|
<3.5mA / 240VAC
|
PROTECTION
|
OVER LOAD
|
105 ~ 150% rated output power
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
SHORT CIRCUIT
|
|
OVER VOLTAGE
|
30 ~ 36V
|
54 ~ 66V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
OVER TEMP
|
100 5 (TSW : detect on heatsink of power switch)
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
OTHERS
|
MTBF
|
187.9Khrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
227*125.2*100mm (W*H*D)
|
PACKING
|
2.6Kg; 6pcs / 16.6Kg / 1.75CUFT
|