MODEL
|
SPV-1500-12
|
SPV-1500-24
|
SPV-1500-48
|
OUTPUT
|
DC VOLTAGE
|
12V
|
24V
|
48V
|
CURRENT RANGE
|
0 ~ 125A
|
0 ~ 63A
|
0 ~ 32A
|
RATED CURRENT
|
125A
|
63A
|
32A
|
RATED POWER
|
1500W
|
1512W
|
1536W
|
RIPPLE & NOISE (max.) Note.2
|
150mVp-p
|
150mVp-p
|
200mVp-p
|
VOLTAGE ADJ. RANGE
|
5% typical adjustment by VR, 20% ~ 110% (typ.) adjustment by 1~6VDC external control signal
|
VOLTAGE TOLERANCE
NOTE.3
|
1.0%
|
1.0%
|
1.0%
|
LINE REGULATION
|
0.5%
|
0.5%
|
0.5%
|
LOAD REGULATION
|
0.5%
|
0.5%
|
0.5%
|
SETUP, RISE TIME NOTE.5
|
1500ms, 100ms at full load
|
HOLD UP TIME (Typ.)
|
10ms at full load 14ms at full load 16ms at full load
|
INPUT
|
VOLTAGE RANGE
|
90 ~ 264VAC 127 ~ 370VDC
|
FREQUENCY RANGE
|
47 ~ 63Hz
|
POWER FACTOR (Typ.)
|
0.95/230VAC 0.98/115VAC at full load
|
EFFICIENCY (Typ.)
|
86.5%
|
90%
|
90%
|
AC CURRENT (Typ.)
|
17A/115VAC 8A/230VAC
|
INRUSH CURRENT (Typ.)
|
30A/115VAC 60A/230VAC
|
LEAKAGE CURRENT
|
<2.0mA / 240VAC
|
PROTECTION
|
OVER LOAD
|
105 ~ 135% rated output power
|
Protection type : Constant current limiting, recovers automatically after fault condition is removed
|
OVER TEMPERATURE
|
105 5 (TSW2 ) detect on heatsink of power transistor
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
OVER VOLTAGE
|
13.8 ~ 16.8V
|
30 ~ 34.8V
|
57.6 ~ 67.2V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
FUNCTION
|
AUXILIARY POWER(AUX)
|
12V@0.1A(Only for Remote ON/OFF control)
|
REMOTE ON/OFF CONTROL
|
Please see the Function Manual
|
ALARM SIGNAL OUTPUT
|
Please see the Function Manual
|
OUTPUT VOLTAGE TRIM
|
2.4~13.2V
|
4.8 ~ 28V
|
9.6 ~ 56V
|
ENVIRONMENT
|
WORKING TEMP.
|
-20 ~ +70oC (Refer to output load derating curve)
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-40 ~ +85oC , 10 ~ 95% RH
|
TEMP. COEFFICIENT
|
0.05%/oC(0 ~ 50oC)
|
VIBRATION
|
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
|
SAFETY &EMC
|
SAFETY STANDARDS
|
UL60950-1, TUV EN60950-1 approved
|
WITHSTAND VOLTAGE
|
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
ISOLATION RESISTANCE
|
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
|
EMI CONDUCTION & RADIATION
|
Compliance to EN55022 (CISPR22)
|
HARMONIC CURRENT
|
Compliance to EN61000-3-2,-3
|
EMS IMMUNITY
|
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
|
OTHERS
|
MTBF
|
109K hrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
278*127*83.5mm (L*W*H)
|
PACKING
|
2.6Kg; 6pcs/16.6Kg/1.54CUFT
|
NOTE
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25oCof ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The nbsp;power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.