MODEL
|
RSP-2400-12
|
RSP-2400-24
|
RSP-2400-48
|
OUTPUT
|
DC VOLTAGE
|
12V
|
24V
|
48V
|
CURRENT RANGE
|
0 ~ 166.7A
|
0 ~ 100A
|
0 ~ 50A
|
RATED CURRENT
|
166.7A
|
100A
|
50A
|
RATED POWER
|
2000.4W
|
2400W
|
2400W
|
RIPPLE & NOISE
|
150mVp-p
|
150mVp-p
|
200mVp-p
|
VOLTAGE ADJ. RANGE
|
10.8 ~ 13.2V
|
22 ~ 28V
|
43 ~ 56V
|
VOLTAGE TOLERANCE
|
1.0%
|
1.0%
|
1.0%
|
LINE REGULATION
|
0.5%
|
LOAD REGULATION
|
0.5%
|
0.5%
|
0.5%
|
SETUP, RISE TIME NOTE.5
|
1000ms, 80ms at full load
|
HOLD UP TIME (TYP)
|
12ms at full load
|
INPUT
|
VOLTAGE RANGE
|
180 ~ 264VAC 254 ~ 370VDC
|
FREQUENCY RANGE
|
47 ~ 63Hz
|
POWER FACTOR (Typ.)
|
0.95/230VAC at full load
|
EFFICIENCY (Typ.)
|
87%
|
90%
|
91.5%
|
AC CURRENT (Typ.)
|
15.5A/180VAC 12A/230VAC
|
INRUSH CURRENT (Typ.)
|
60A/230VAC
|
LEAKAGE CURRENT
|
<2.0mA / 240VAC
|
PROTECTION
|
OVER LOAD
|
100 ~ 112% rated output power
|
User adjustable continuous constant current limiting .or constant current limiting with delay shutdown after 5 seconds, re-power on to recover
|
OVER VOLTAGE
|
13.8 ~ 16.8V
|
28.8 ~ 33.6V
|
57.6 ~ 67.2V
|
Protection type : Shut down o/p voltage, re-power on to recover
|
OVER TEMPERATURE
|
95 oC 5 (12V), 100oC 5 (24V,48V) (TSW1: detect on heatsink of power transistor)
|
95oC 5 (12V), 85oC 5 (24V), 80 5 (48V) (TSW2 : detect on heatsink of o/p diode)
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
FUNCTION
|
AUXILIARY POWER
|
12V@0.1A(Only for Remote ON/OFF control)
|
REMOTE CONTROL
|
Please refer to function manual
|
CURRENT SHARING
|
Please refer to function manual
|
OUTPUT VOLTAGE TRIM
|
2.4 ~ 13.2V
|
4.8 ~ 28V
|
9.6 ~ 56V
|
CURRENT SHARING
|
Please see the Function Manual
|
ENVIRONMENT
|
WORKING TEMP.
|
-20 ~ +70oC (Refer to output load derating curve)
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-40 ~ +85oC , 10 ~ 95% RH non-condensing
|
TEMP. COEFFICIENT
|
0.05%/oC (0 ~ 50oC )
|
VIBRATION
|
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
|
SAFETY &EMC
|
SAFETY STANDARDS
|
UL60950-1, TUV EN60950-1 approved
|
WITHSTAND VOLTAGE
|
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
ISOLATION RESISTANCE
|
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
|
EMI CONDUCTION & RADIATION
|
Compliance to EN55022 (CISPR22)
|
HARMONIC CURRENT
|
Compliance to EN61000-3-2,-3
|
EMS IMMUNITY
|
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
|
OTHERS
|
MTBF
|
106.7K hrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
278*177.8*63.5mm (L*W*H)
|
PACKING
|
3.3Kg; 4pcs/14.2Kg/1.89CUFT
|
NOTE
|
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25oCof ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
|