MODEL
|
MPS-30-5
|
MPS-30-12
|
MPS-30-15
|
MPS-30-24
|
MPS-30-27
|
MPS-30-48
|
OUTPUT
|
DC VOLTAGE
|
5V
|
12V
|
15V
|
24V
|
27V
|
48V
|
RATED CURRENT
|
5A
|
2.5A
|
2A
|
1.2A
|
1.1A
|
0.6A
|
CURRENT RANGE
|
0 ~ 5A
|
0 ~ 2.5A
|
0 ~ 2A
|
0 ~ 1.2A
|
0 ~ 1.1A
|
0 ~ 0.6A
|
RATED POWER
|
25W
|
30W
|
30W
|
28.8W
|
29.7W
|
28.8W
|
RIPPLE & NOISE
|
80mVp-p
|
120mVp-p
|
150mVp-p
|
240mVp-p
|
240mVp-p
|
240mVp-p
|
VOLTAGE TOLERANCE
|
3.0%
|
3.0%
|
3.0%
|
3.0%
|
3.0%
|
2.0%
|
LINE REGULATION
|
1.0%
|
1.0%
|
0.5%
|
0.5%
|
0.5%
|
0.5%
|
LOAD REGULATION
|
2.0%
|
1.0%
|
1.0%
|
1.0%
|
1.0%
|
1.0%
|
SETUP, RISE TIME
|
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
|
HOLD UP TIME
|
70ms/230VAC 12ms/115VAC at full load
|
INPUT
|
VOLTAGE RANGE
|
88 ~ 264VAC auto switch 120 ~ 370VDC
|
FREQUENCY
|
47 ~ 63Hz
|
EFFICIENCY (Typ.)
|
72%
|
75%
|
76%
|
77%
|
78%
|
78%
|
AC CURRENT
|
0.8A/115VAC 0.5A/230VAC
|
INRUSH CURRENT
|
COLD START 30A/230VAC
|
LEAKAGE CURRENT
|
<0.3mA / 264VAC
|
PROTECTION
|
OVER LOAD
|
Above 105% rated output power
|
Protection type : Hiccup mode, recovers automatically after fault condition is removed
|
OVER VOLTAGE
|
5.5 ~ 6.75V
|
13.2 ~ 16.2V
|
16.5 ~ 20.25V
|
26.4 ~ 32.4V
|
29.7 ~ 36.45V
|
52.8 ~ 64.8V
|
Protection type : Hiccup mode, recovers automatically after fault condition is removed
|
ENVIRONMENT
|
WORKING TEMP.
|
-10 ~ +60oC (Refer to output load derating curve)
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-20 ~ +85oC , 10 ~ 95% RH
|
TEMP. COEFFICIENT
|
0.03%/ oC (0 ~ 50oC ) on +5V output
|
VIBRATION
|
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
|
SAFETY &EMC
|
SAFETY STANDARDS
|
UL2601-1, TUV EN60601-1, IEC60601-1 approved
|
WITHSTAND VOLTAGE
|
I/P-O/P:4KVAC I/P-FG:1.5KVAC O/P-FG:SHORT
|
ISOLATION RESISTANCE
|
I/P-O/P, I/P-FG:100M Ohms/500VDC
|
EMI CONDUCTION & RADIATION
|
ompliance to EN55011 (CISPR11) Class B
|
HARMONIC CURRENT
|
Compliance to EN61000-3-2,-3
|
EMS
IMMUNITY
|
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, EN60601-1-2, medical level, criteria A
|
MTBF
|
547Khrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
101.6*65.8*23.5mm (L*W*H)
|
PACKING
|
0.16Kg; 90pcs/15.8Kg/1.02CUFT
|
NOTE
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25oCof ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
|