MODEL
|
USP-150-12
|
USP-150-15
|
USP-150-24
|
USP-150-36
|
USP-150-48
|
OUTPUT
|
DC VOLTAGE
|
12V
|
15V
|
24V
|
36V
|
48V
|
CURRENT RANGE
|
0 ~ 12.5A
|
0 ~ 10A
|
0 ~ 6.3A
|
0 ~ 4.2A
|
0 ~ 3.2A
|
RATED CURRENT
|
12.5A
|
10A
|
6.3A
|
4.2A
|
3.2A
|
RATED POWER
|
150W
|
150W
|
151.2W
|
151.2W
|
153.6W
|
RIPPLE & NOISE (max.) Note.2
|
100mVp-p
|
150mVp-p
|
150mVp-p
|
250mVp-p
|
250mVp-p
|
VOLTAGE ADJ. RANGE
|
11.0~13.2V
|
13.5~16.5V
|
21.6~26.4V
|
32.4~39.6V
|
43.2~52.8V
|
VOLTAGE TOLERANCE
NOTE.3
|
2.0%
|
LINE REGULATION
|
0.5%
|
LOAD REGULATION
|
1.0%
|
SETUP, RISE TIME NOTE.5
|
2000ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
|
HOLD UP TIME (Typ.)
|
16ms/230VAC 16ms/115VAC at full load
|
INPUT
|
VOLTAGE RANGE
|
90 ~ 295VAC 127 ~ 417VDC
|
FREQUENCY RANGE
|
47 ~ 63Hz
|
EFFICIENCY (Typ.)
|
91.5%
|
91.5%
|
93%
|
93%
|
93%
|
AC CURRENT (Typ.)
|
2A/115VAC 1A/230VAC
|
INRUSH CURRENT (Typ.)
|
Cold start 65A/230VAC
|
LEAKAGE CURRENT
|
<2mA / 240VAC
|
PROTECTION
|
OVER LOAD
|
145~185% rated output power
|
Protection type : Hiccup mode, recovers automatically after fault condition is removed
|
OVER VOLTAGE
|
13.6~16.3V
|
17 ~ 21V
|
26.7~32.4V
|
41.4~48.6V
|
53 ~ 64.8V
|
Protection type : Hiccup mode, recovers automatically after fault condition is removed
|
OVER TEMPERATURE
|
100 5 (RTH2)
|
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
|
ENVIRONMENT
|
WORKING TEMP.
|
-30 ~ +65oC (Refer to output load derating curve)
|
WORKING HUMIDITY
|
20 ~ 90% RH non-condensing
|
STORAGE TEMP., HUMIDITY
|
-40 ~ +85oC , 10 ~ 95% RH
|
TEMP. COEFFICIENT
|
0.03%/oC (0 ~ 60oC)
|
VIBRATION
|
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
|
SAFETY &EMC
|
SAFETY STANDARDS
|
IEC60950-1,UL60950-1,EN60950-1 approved
|
WITHSTAND VOLTAGE
|
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
|
ISOLATION RESISTANCE
|
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/25 / 70%RH
|
EMI CONDUCTION & RADIATION
|
Compliance to EN55022 (CISPR22) Class B
|
HARMONIC CURRENT
|
Compliance to EN61000-3-2,EN61000-3-3
|
EMS
IMMUNITY
|
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level (surge 4KV), criteria A
|
OTHERS
|
MTBF
|
216.3K hrs min. MIL-HDBK-217F (25 )
|
DIMENSION
|
215*67.4*33mm (L*W*H)
|
PACKING
|
0.48kg; 24PCS/12.5kg/0.61CUFT
|
NOTE
|
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25oCof ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the static characteristics for more details.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
|